Lead Wires
PTFE insulated, silver plated, 24-gauge stranded copper wire
Time Constant / Response
12 seconds maximum required to reach 63.2% sensor response in water flowing at 3 ft/s (0.91 m/s)
Stability
±0.11% 0.28 °C or 0.51 °F maximum ice-point resistance shift following 1,000 hours at maximum specified temperature (400 °C)
Insulation Resistance
1000 x 10^6 ohms minimum insulation resistance when measured at 500 Vdc at room temperature
Calibration Options
Calibration schedule or customer-specified calibration range, both with Callendar-Van Dusen constants